СРАВНИТЕЛЬНЫЙ АНАЛИЗ МЕТОДОВ ВНИИПО И ME-TNOДЛЯ ПРОГНОЗИРОВАНИЯ ВЗРЫВОВ ПАРОВОЗДУШНЫХ СМЕСЕЙ В ЗАКРЫТЫХ ПОМЕЩЕНИЯХ

Translated title of the contribution: COMPARATIVE ANALYSIS OF THE METHODS OF VNIIPO AND ME-TNO FOR FORECASTING OF VCE IN CLOSED ROOMS

Сергей Геннадьевич Алексеев, Евгений Сергеевич Гурьев, Людмила Владимировна Полуян, Николай Михайлович Барбин

Research output: Contribution to journalArticle

Abstract

On the example of 80 main organic solvents, a comparative analysis of the VNIIPO and ME-TNO methods has carried out for vapor cloud explosions (VCE) in closed rooms. The specific safe volume of the room is chosen as the compari- son parameter. The correlation between the results of calculations for these methods is found. The 3-th class VCE of ME-TNO with the correction factor 1,42 can be used to categorize production facilities for explosion and fire hazard.
Translated title of the contributionCOMPARATIVE ANALYSIS OF THE METHODS OF VNIIPO AND ME-TNO FOR FORECASTING OF VCE IN CLOSED ROOMS
Original languageRussian
Pages (from-to)37-45
Number of pages9
JournalКокс и химия
Issue number9
Publication statusPublished - 2017

GRNTI

  • 81.93.00

Level of Research Output

  • VAK List

Fingerprint Dive into the research topics of 'COMPARATIVE ANALYSIS OF THE METHODS OF VNIIPO AND ME-TNO FOR FORECASTING OF VCE IN CLOSED ROOMS'. Together they form a unique fingerprint.